You are here:

KTY Temperature Transmitter DT 45600

Temperature Measuring with KTY Sensors, configurable via DIP Switch or USB

The KTY Temperature Transmitter DT 45600 is used for measure industrial process signals. It converts KTY sensor signals to isolated standard signals.

  • Measuring input for all KTY temperature sensors
    calibrated standard measuring ranges, ready to use
  • Easy configurable via DIP switches
    or via USB interface without auxiliary power supply
  • Switchable Service Functions
    for an easy commissioning
  • 3-port isolation
    Protection against erroneous measurements due to parasitic voltages or ground loops
  • Extremely slim design
    6.2 mm slim housing for a simple and space saving DIN rail mounting
  • Optional In-Rail-Bus mounting rail connector
    allows for fast and economical installation
  • Protective Separation acc. to EN 61140
    Protects service personnel and downstream devices against impermissibly high voltage
  • 5 Years Warranty
    Defects occurring within 5 years from delivery date shall be remedied free of charge at our plant (carriage and insurance paid by sender)

Due to the easy setting of the calibrated measuring ranges via DIP switch the Transmitter is suitable for flexible use.

With the USB Programming-Kit DRAGOset the Transmitter can be configured and all data can be stored by a PC. In mode of programming no additionally auxiliary power is required.

The Commissioning Function, switchable on front panel, generates an output reference signal for testing and adjusting of the downstream signal path.

The auxiliary power can be supplied via the connection terminals or via the optional In- Rail-Bus connector. The status of power supply and sensor connection will be displayed by a LED on front.

Product line

Product line DT 45600
Device Type Order No.
KTY Temperature Transmitter,
programmable via USB and DIP switch
DT 45600 S
KTY Temperature Transmitter,
programmable via USB and DIP switch, In-Rail-Bus for power supply
DT 45600 B

Technical Data

Input

Sensor KT100, KT110, KT130, KT210, KT230,
KTY10-5, KTY10-6, KTY10-62, KTY10-7, KTY11-5, KTY11-6, KTY11-7, KTY13-5,
KTY13-6, KTY13-7,
KTY16-6, KTY19-6M, KTY19-6Z, KTY21-5, KTY21-6, KTY21-7, KTY23-5, KTY23-6, KTY23-7,
KTY81-110, KTY81-120, KTY81-121, KTY81-122, KTY81-210, KTY81-220,
KTY81-221, KTY81-222, KTY81-250, KTY81-251, KTY81-252,
KTY82-110, KTY82-120, KTY82-121, KTY82-122, KTY82-150, KTY82-151, KTY82-152,
KTY82-210, KTY82-220, KTY82-221, KTY82-222, KTY82-250, KTY82-251, KTY82-252,
KTY83-110, KTY83-120, KTY83-121, KTY83-122, KTY83-150, KTY83-151, KTY83-152,
KTY84-130, KTY84-150, KTY84-151, KTY84-152, ST-13, ST-15, ST-16, ST-20M, ST-20Z
Measuring range calibrated steps of 25 °C in complete sensor measuring ranges,
configurable via DIP switch or USB interface
Measuring span min. 25 K
Measuring error < 0.3 K + 0.05 % meas. val.
Sensor connection 3-wire, 2-wire
Sensor current 0.2 mA
Cable resistance < 100 Ohm per wire at 3-wire connection

Output

  Current Voltage
Output signal 0 to 20mA, 4 to 20mA 0 to 5V, 0 to 10V
Load ≤ 12 V   (600 Ohm @ 20 mA) ≤ 5 mA   (2 kOhm @ 10 V)
Residual ripple < 10 mVrms
transfer range 0 to 102.5 %  (3.8 to 20.5 mA at output 4 to 20 mA) Transfer characteristic rising/falling
Error signal Sensor/wire break, error signal programmable

General Data

Transmission error < 0.1 % full scale
Temperature coefficient1) < 100 ppm/K
Sampling rate 4/s
Response time T99 250 ms
Test voltage 3 kV AC, 50 Hz, 1 min Input against output against power supply
Working voltage 2)
(basic insulation)
600 V AC/DC for overvoltage category II and pollution
degree 2 acc. to EN 61010-1
Protection against
electric shock 2)
Protective Separation by reinforced insulation acc. to EN 61010-1
up to 300 V AC/DC for overvoltage category II and contamination
class 2 between input and output and power supply.
Ambient temperature Operation
Transport and storage
-25 °C to +70 °C
-40 °C to +85 °C
(-13 to +158 °F)
(-40 to +185 °F)
Power supply 24 V DC, voltage range 9.6 V to 31.2 V DC, approx. 0.8 W
EMC 3) EN 61326-1
Approvals UL (USA/Canada): UL 61010, Class I, Div. 2
ATEX / IECEx: Zone 2 (nA)
Construction 6.2 mm (0.244") housing, protection type: IP 20
mounting on 35 mm DIN rail acc. to EN 60715
Connection Captive plus-minus clamp screws
Wire cross-section max. 2.5 mm² / AWG 14
Stripped length 6 to 8 mm / 0.28 in
Screw terminal torque 0.8 Nm / 7 lbf in
Weight Approx. 70 g
  1. Average TC related to full scale value in specified operating temperature range, reference temperature 23 °C
  2. For applications with high working voltages, ensure there is sufficient spacing or isolation from neighboring devices and protection against electric shocks.
  3. Minor deviations possible during interference

Block diagram

Dimensions

Terminal assignments

  • 1 + Input KTY
  • 2 + Input 3-wire
  • 3 -
  • 4 − Input KTY
  • 5 + Output
  • 6 − Output
  • 7 + Power supply 24 V DC
    (connected to In-Rail-Bus)
  • 8 − Power supply 24 V DC
    (connected to In-Rail-Bus)

Optional power connection via In-Rail-Bus (see accessories)

Subject to change!

Back to the product list

Product request

Please add 1 and 1.