Standard Signal AI Module DMB 96100

Measuring input for Standard Signals, Modbus RTU

  • Input for Standard Signals
  • In-Rail-Bus Connector for Modbus and power supply
  • Protective Separation up to 300 V AC/DC, test voltage 3 kV
  • Easy configurable via DIP switches or Modbus interface
  • Freely scalable up to 247 measuring inputs in one Modbus segment
  • Extremly slim, only 6.2 mm installation width
  • Made in Germany
  • 5 Years Warranty

The Modbus Standard Signal AI Module is used for electrical isolated conversion of unipolar standard voltage and current signals. All parameter can be set via Modbus RTU Interface. A subset of the most common settings is available via DIP switches.

The measuring value can be read over the Modbus RTU (RS485) interface.

The 2-way isolation guarantees reliable decoupling of the sensor circuit from the processing circuit and the auxiliary power circuit. Auxiliary power and Modbus RTU can be connected via the connection terminals or via the In-Rail-Bus connector (see accessories).

Technical Data

Input

  Voltage Current
Input signal 0 to 10 V
2 to 10 V
0 to 5 V
1 to 5 V
0 to 20 mA
4 to 20 mA
Input resistance ≥ 100 kOhm ≤ 25 Ohm
Overload ≤ 30 V ≤ 50 mA
Transmitter supply 16 V (open circuit/short circuit < 22 V/35 mA)

Modbus

Protocol Modbus RTU (RS485)
Module addressing 1 to 247
Response delay 1 to 1000 ms
Baud rate 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Configuration Parity: Even, Odd, None with 2 stop bits, None with 1 stop bit
Connectivity Up to 247 DRAGO Modbus devices without additional repeater (1/8 Load)
Indication Yellow LED on front panel
Measuring range 0 to 115 %

General Data

Measuring error < 0.1 % full scale
Temperature coefficient1) < 100 ppm/K
Sampling rate up to 100/s (a moving average filter with a width of 10 samples is applied internal)
Test voltage 3 kV AC, 50 Hz, 1 min., Input against Modbus/power supply
Working voltage2)
(Basic insulation)
600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1
Protection against dangerous body currents2) Protective Separation by reinforced insulation acc. to DIN EN 61010-1 up to 300 V AC/DC for overvoltage category II and contamination class 2 between input and Modbus/power supply
Ambient temperature Operation: -25 °C to +70 °C
Transport and storage: -40 °C to +85 °C
Power supply 24 V DC, Voltage range 16.8 V to 31.2 V DC, max. 1.3 W
EMC3) EN 61326-1
Construction 6.2 mm (0.244") housing, protection type: IP 20, mounting on 35 mm DIN rail acc. to EN 60715
Connection
(captive plus-minus clamp screws)
Solid: 0.5 mm2 - 4 mm2 / AWG 20-12
Fine-stranded: 0.5 mm2 - 2.5 mm2 / AWG 20-14
Stripped length: 6-8 mm / 0.28 in
Screw terminal torque 0.8 Nm / 7 lbf in
Weight Approx. 70 g
  1. Average TC related to full scale in specified operating temperature range, reference temperature 23 °C
  2. As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipment. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
  3. Minor deviations possible during interference

Block diagram

<p>Modbus Normsignal AI Modul DMB 96100<br>Modbus Standard Signal AI Module DMB 96100</p>

Dimensions

Masszeichnung-mitModbus

Terminal assignments

1 + Transmitter Supply Tx
2 + Input U
3 + Input I
4 Input GND
     
5   Modbus A (connected to In-Rail-Bus A)
6   Modbus B (connected to In-Rail-Bus B)
     
7 + Power supply (connected to In-Rail-Bus D)
8 Power supply (connected to In-Rail-Bus C)

Downloads

Product line

Item Order No.
Modbus Standard Signal AI Module,
In-Rail-Bus for power supply and Modbus connection
DMB 96100 B
In-Rail-Bus see accessories  
Subject to change!