You are here:

Signal Splitter/Repeater DN 21000

Isolation, Conversion and Loop Supply of Standard Signals with 2 Outputs

The Signal Splitter/Repeater DN 21000 is used for isolation, conversion and distribution of 0/4 to 20 mA, 0/1 to 5 V and 0/2 to 10 V standard signals. The measuring input can also supply the loop power for 2-wire transmitters.

  • Universal configurable operating
    Signal isolator or repeater power supply for 2-wire transmitters, 2 independent outputs
  • Calibrated signal setting
    Input and output range can be set by using DIP switch – high precision without any further adjustment
  • 4-Port isolation
    Protection against erroneous measurements due to parasitic voltages or ground loops
  • Extremely slim design
    6.2 mm slim housing for a simple and space saving DIN rail mounting
  • Optional In-Rail-Bus mounting rail connector
    allows for fast and economical installation
  • Protective Separation acc. to EN61140
    Protects service personnel and downstream devices against impermissibly high voltage
  • Maximum reliability
    No maintenance costs
  • 5 Years Warranty
    Defects occurring within 5 years from delivery date shall be remedied free of charge at our plant (carriage and insurance paid by sender)

The input and two isolated outputs can be easily configured by using DIP switch. Due to the calibrated range selection no further adjustment is necessary.

The auxiliary power can be supplied via the connection terminals or via the optional In- Rail-Bus connector. A green LED on the front of the unit has been provided to monitor the power supply.

Product line

Product line DN 21000
Device Type Order No.
Signal Splitter/Repeater, calibrated range selection DN 21000 S
Signal Splitter/Repeater, calibrated range selection,
In-Rail-Bus for power supply
DN 21000 B

Technical Data

Input

Input signal
(calibrated switchable)
0 to 20 mA, 4 to 20 mA, 0 to 5 V, 0 to 10 V, 1 to 5 V, 2 to 10 V
Input resistance Current input
Voltage input
≤ 35 Ohm
≥ 100 kOhm
Overload Current input
Voltage input
< 50 mA
< 30 V
Transmitter supply Tx
(switchable)
16 V (open circuit voltage/short circuit current ≤ 22 V/35 mA)

Output I + II

Output signal
(calibrated switchable)
0 to 20 mA, 4 to 20 mA, 0 to 5 V, 0 to 10 V, 1 to 5 V, 2 to 10 V
Load Current output: ≤ 6 V (300 Ohm at 20 mA) Voltage output: ≤ 5 mA (2 kOhm at 10 V)
Linear transmission range -1 to +110 %
Residual ripple < 10 mVrms

General Data

Transmission error < 0.1 % full scale
Temperature coefficient 1) < 100 ppm/K
Cut-off frequency -3 dB 5 kHz
Response time T99 150 µs
Test voltage 3 kV AC, 50 Hz, 1 min, Input against Output I against Output II
against power supply
Working voltage 2)
(Basic Insulation)
600 V AC/DC for overvoltage category II and pollution degree 2
acc. to EN 61010-1
Protection against
electrical shock
Protective separation according to EN 61140 by reinforced
insulation in accordance with EN 61010-1 up to 300 V AC/DC
for overvoltage category II and pollution degree 2 between all circuits.
Ambient temperature Operation
Transport and storage
–25 °C to +70 °C   (-13 to +158 °F)
–40 °C to +85 °C   (-40 to +185 °F)
Power supply 24 V DC, voltage range 16.8 V to 31.2 V DC, approx. 1.4 W
EMC 3) EN 61326-1
Approvals UL (USA/Canada): UL 61010, Class I, Div. 2
ATEX / IECEx: Zone 2 (nA)
Construction 6.2 mm (0.244") housing, protection class: IP 20
mounting on 35 mm DIN rail acc. to EN 60715
Connection Captive plus-minus clamp screws
Wire cross-section max. 2.5 mm² / AWG 14
Stripped length 6 to 8 mm / 0.28 in
Screw terminal torque 0.8 Nm / 7 lbf in
Weight Approx. 70 g
  1. Average TC related to full scale value in specified operating temperature range, reference temperature 23 °C
  2. For applications with high working voltages, ensure there is sufficient spacing or isolation from neighboring devices and protection against electric shocks.
  3. Minor deviations possible during interference

Block diagram

Dimensions

Terminal assignments

  • 1 Input -I +U +Loop
  • 2 Input +I -U -Loop
  • 3 + Output II
  • 4 − Output II
  • 5 + Output I
  • 6 − Output I
  • 7 + Power supply 24 V DC
    (connected to In-Rail-Bus)
  • 8 − Power supply 24 V DC
    (connected to In-Rail-Bus)

Optional power connection via In-Rail-Bus (see accessories)

Subject to change!