Temperature Transmitter D62T 45300

for Pt, Ni and TC Standard-Sensors, programmable per USB and DIP switch

The Temperature Transmitter D62T 45300 converts the sensor signal on input to temperature linear standard signal 0/4 to 20 mA or 0 to 5/10 V.

  • Universal Temperature Measuring Input
    for Platinum, Nickel and Thermocouple Standard Sensors
  • Easy configurable per USB or DIP switch
    Sensor type, measuring range, sensor connection und output signal easy programmable per USB interface - without supply power - or calibrated range selection per DIP switch
  • 3-port isolation
    Protection against erroneous measurements due to parasitic voltages or ground loops
  • Extremely slim design
    6.2 mm thin housing for DIN rail mounting
  • Cross-connector for the auxiliary power supply
    fast and economical installation
  • Protective Separation acc. to EN 61140
    Protects service personnel and downstream devices against impermissibly high voltage
  • Maximum reliability
    No maintenance costs
  • 5 Years Warranty
    Defects occurring within 5 years from delivery date shall be remedied free of charge at our plant (carriage and insurance paid by sender)

Due to the easy configuration via USB interface and the calibrated range selection per DIP switch the Transmitter is suitable for flexible use. The high reliability and the protective separation are further features, which ensure a safe system operation.

With the USB Programming-Kit DRAGOset the Transmitter can be configured and all data can be stored by a PC. In mode of programming no additionally auxiliary power is required.

Pluggable cross-connectors for the auxiliary power supply ensure fast and economical installation. The slim housing with 6.2 mm wide saves significant space on DIN-rail in the switch cabinet.

The optimized efficiency of the D62T 45300 power pack contributes a significant reduction of the unit’s own heat generation. This is reflected in extremely high MTBF, which means highest reliability and long-term stability. A green LED on the front of the unit has been provided to monitor the power supply. The status of power supply and sensor connection will be displayed by a LED on front.

Product line

Product line D62T 45300
Devices Order No.
Temperature Transmitter D62T 45300

Data sheet archive:

The products are no longer available!

Technical Data

Input

Resistance Thermometer Sensor Measuring range min. Span
    Pt 100 -200 °C to +850 °C 50 K
    Pt 1000 -200 °C to +850 °C 50 K
    Ni 100 -50 °C to +175 °C 50 K
  Measuring error max. < 0.1 K / 0.05 %
  Temperature influence < 50 ppm/K
  Sensor connection 4-wire, 3-wire, 2-wire
  Cable resistance < 100 Ohm per wire
  Sensor current 0.2 mA
  Diagnostic function Sensor / wire break, Error signal on output programmable
Thermocouples Sensor Measuring range min. Span
    Type J -200 °C to +1200 °C 50 K
    Type K -200 °C to +1375 °C 50 K
  Measuring error max. < 0.3 K / 0.1 %
  Temperature influence < 50 ppm/K
  Cold junction compensation internal, external, uncompensated
  Error of Cold junction, internal < 1.5 K
  Diagnostic function Sensor / wire break, Error signal on output programmable

Output

  Current Voltage
Output signal 0 to 20 mA, 4 to 20 mA 0 to 5 V, 0 to 10 V
Load ≤ 12 V     (600 Ohm @ 20 mA) ≤ 5 mA     (2 kOhm @ 10 V)
Offset < 20 µA < 10 mV
Linear transfer range 0 to 102.5 % FSR
(3.8 to 20.5 mA at Output 4 to 20 mA)
Error signal 0 % / 110 % of output range, programmable
Residual ripple < 10 mVrms

General Data

Transfer characteristic Rising / falling linearly
Transmission error < 0.1 %
Temperature coefficient 1) < 100 ppm/K full scale
Measurement rate 4 / s
Test voltage 2.5 kV, 50 Hz Input against output against power supply
Working voltage 2)
(basic insulation)
600 V AC/DC for overvoltage category II and contamination class 2
acc. to EN 61010 part 1
Protection against
electric shocke 2)
Protective Separation by reinforced insulation acc. to EN 61010 part 1
up to 300 V AC/DC for overvoltage category II and contamination
class 2 between input and output and power supply.
Ambient temperature Operation
Transport and storage
-25 °C to +70 °C
-40 °C to +85 °C
(-13 to +158 °F)
(-40 to +185 °F)
Power supply 24 V DC 16.8 V to 31.2 V DC, approx. 0.8 W
EMC 3) EN 61326-1
Construction 6.2 mm housing, protection type: IP 20
Weight approx. 50 g

Bold: Factory setting:
Input Pt100, 0 to 100 °C, 4-wire, Output 0 to 20 mA, transfer characteristic rising, error signal 22 mA

  1. Average TC in specified operating temperature range
  2. As far as practicable the standards and rules mentioned above are considered by development and production of our devices. In addition the assembly rules for our devices are to be considered by installation in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
  3. Minor deviations possible during interference

Block diagram

Dimensions

Terminal assignments

  • 1 Input
  • 2 Input
  • 3 Input
  • 4 Input
  • 5 + Output
  • 6 − Output
  • 7 + Power supply 24 V DC
  • 8 − Power supply 24 V DC

Connections
Screw terminals, wire cross-section max. 1.5 mm²

Subject to change!

Back to the product list

Product request