<p>Sondersignal-Trennverstärker DK 8000<br />Customer-Specific Isolation Amplifier DK 8000</p>
Goto Service Web Portal
Webinfo 4 Easy
Webinfo 4 Easy :: 103

Customer-Specific Isolation Amplifier DK 8000

Isolation and Conversion of Industrial Signals in Special Applications

With the Isolation Amplifier DK 8000 DRAGO is extending its offer on high-functional and high-reliable components of customer-specific solutions.

  • Customer-Specific Solutions
    Special Input ant output range on request
  • Universal Power Supply for 20...253 V AC/DC
    Applicable world-wide for all common supply voltages
  • 3-port isolation
    Protection against erroneous measurements due to parasitic voltages or ground loops
  • Ultra-small-sized housing
    12.5 mm housing with plug-in screw terminal blocks
  • High accuracy
    No falsification of measured signal
  • Protective Separation
    Protects service personnel and downstream devices against impermissibly high voltage
  • Maximum reliability
    No maintenance costs
  • 5 Years Warranty

The Isolation Amplifier DK 8000 is used for isolation and conversion of customer-specific industrial signals. When it comes to individualized solutions, the know-how advantage of our development team stands ready to serve. This allows us to offer customer-specific solutions with the proverbial DRAGO quality in the shortest possible time; solutions which, as a result of individualized consultation, optimally meet all customer needs, including their economic ones.

The order key allows you to select the desired input and output ranges to which the unit will be adjusted at the factory before delivery. These can be easily reconfigured at any time by means of DIP switch settings. Subsequent readjustment or a measured range compensation can then be performed at the zero/span potentiometers on the front panel. Also the cut-off frequency can be adapted to the measurement task by using the DIP Switch.

The slim housing with 12.5 mm width saves space in the switch cabinet and facilitates by the practical plug-in screw terminal blocks the assembly.

The new universal power pack for 20...253 V AC/DC means the DK 8000 can be used anywhere in the world, with all mains power supplies. The unit’s high efficiency contributes significantly to reducing the unit’s own heat generation. This is reflected in extremely high reliability and long-term stability.

Technical Data

Input

Input signalscustomer-specific technical data as orders (see label)
Input resistance
Current input
Voltage input
approx. 25 Ohm (depends on measuring range)
approx. 1 MOhm (depends on measuring range)
OverloadMax. 120 % of final value

Output

Output signalscustomer-specific technical data as orders (see label)
LoadCurrent output
Voltage output
≤ 12 V (600 Ohm at 20 mA)
≤ 20 mA (500 Ohm at 10 V)
Transmission rangeunipolar: –2 ... +110 %, bipolar: –110 ... +110 %
Ripple< 10 mVrms

General Data

Transmission error0.1 % of final value (max. 0,3 %, depends on measuring range)
Temperature coefficient 1)100 ppm/K of final value
Zero/Span Adjustmentoptional
Cut-off frequency (-3 dB)max. 10 kHz
Test voltage4 kV, 50 Hz
input against output against power supply
Working voltage 2)
(Basic Insulation)
Up to 1000 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010–1 between all circuits.
Ambient temperature
Operation
Transport and storage
–20 °C to +70 °C
–35 °C to +85 °C
Power supply20 ... 253 V AC/DC
AC 48 ... 62 Hz, approx. 2 VA
DC approx. 1.0 W
EMC 3)EMVG, EN 61326 -1
Construction12.5 mm housing, protection class: IP 20
WeightApprox. 100 g
  1. Average TC in specified operating temperature range
  2. As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
  3. Minor deviations possible during interference

Block diagram

Dk8000

Dimensions

GehaeuseHighFunctionality

Terminal assignments
Wire cross-section max. 2.5 mm², Multi-wire connection max. 1 mm² (two wires with same cross-section)

1Input +5Output +
2Input -6Output -
3Input +
7Power supply ~
4Input -8Power supply ~

Product line

DevicesOrder No.
Customer-Specific Isolation AmplifierDK 8000 – XXX
The index number - XXX describes the signal combination
and will be announced by order.
 
Subject to change!