Isolation and Conversion of Industrial Signals in Special Applications
With the Isolation Amplifier DK 8000 DRAGO is extending its offer on high-functional and high-reliable components of customer-specific solutions.
- Customer-Specific Solutions
Special Input ant output range on request - Universal Power Supply for 20...253 V AC/DC
Applicable world-wide for all common supply voltages - 3-port isolation
Protection against erroneous measurements due to parasitic voltages or ground loops - Ultra-small-sized housing
12.5 mm housing with plug-in screw terminal blocks - High accuracy
No falsification of measured signal - Protective Separation
Protects service personnel and downstream devices against impermissibly high voltage - Maximum reliability
No maintenance costs - 5 Years Warranty
The Isolation Amplifier DK 8000 is used for isolation and conversion of customer-specific industrial signals. When it comes to individualized solutions, the know-how advantage of our development team stands ready to serve. This allows us to offer customer-specific solutions with the proverbial DRAGO quality in the shortest possible time; solutions which, as a result of individualized consultation, optimally meet all customer needs, including their economic ones.
The order key allows you to select the desired input and output ranges to which the unit will be adjusted at the factory before delivery. These can be easily reconfigured at any time by means of DIP switch settings. Subsequent readjustment or a measured range compensation can then be performed at the zero/span potentiometers on the front panel. Also the cut-off frequency can be adapted to the measurement task by using the DIP Switch.
The slim housing with 12.5 mm width saves space in the switch cabinet and facilitates by the practical plug-in screw terminal blocks the assembly.
The new universal power pack for 20...253 V AC/DC means the DK 8000 can be used anywhere in the world, with all mains power supplies. The unit’s high efficiency contributes significantly to reducing the unit’s own heat generation. This is reflected in extremely high reliability and long-term stability.
Input
| Input signals | customer-specific technical data as orders (see label) | |
| Input resistance | Current input Voltage input | approx. 25 Ohm (depends on measuring range) approx. 1 MOhm (depends on measuring range) |
| Overload | Max. 120 % of final value | |
Output
| Output signals | customer-specific technical data as orders (see label) | |
| Load | Current output Voltage output | ≤ 12 V (600 Ohm at 20 mA) ≤ 20 mA (500 Ohm at 10 V) |
| Transmission range | unipolar: –2 ... +110 %, bipolar: –110 ... +110 % | |
| Ripple | < 10 mVrms | |
General Data
| Transmission error | 0.1 % of final value (max. 0,3 %, depends on measuring range) | |
| Temperature coefficient 1) | 100 ppm/K of final value | |
| Zero/Span Adjustment | optional | |
| Cut-off frequency (-3 dB) | max. 10 kHz | |
| Test voltage | 4 kV, 50 Hz input against output against power supply | |
| Working voltage 2) (Basic Insulation) | Up to 1000 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010–1 between all circuits. | |
| Ambient temperature | Operation Transport and storage | –20 °C to +70 °C –35 °C to +85 °C |
| Power supply | 20 ... 253 V AC/DC | AC 48 ... 62 Hz, approx. 2 VA DC approx. 1.0 W |
| EMC 3) | EMVG, EN 61326 -1 | |
| Construction | 12.5 mm housing, protection class: IP 20 | |
| Weight | Approx. 100 g | |
- Average TC in specified operating temperature range
- As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
- Minor deviations possible during interference


Terminal assignments
Wire cross-section max. 2.5 mm², Multi-wire connection max. 1 mm² (two wires with same cross-section)
| 1 | Input + | 5 | Output + |
| 2 | Input - | 6 | Output - |
| 3 | Input + | 7 | Power supply ~ |
| 4 | Input - | 8 | Power supply ~ |
| Devices | Order No. |
| Customer-Specific Isolation Amplifier | DK 8000 – XXX |
| The index number - XXX describes the signal combination and will be announced by order. |